HC
GENERATOR RANGE : HCI4 / HCM4
- HCI/HCM 4 is a range of
4-pole, single or 2-bearing AVR controlled generators.
- Engines adaptors to SAE
0, 1/2, 1, 2 & 3 and coupling discs to SAE 111/2, 14 & 18 are
offered for HCI / HCM 4.
- HCKI 4 is a higher
output alternative to HCI 4, dedicated to SAE 2/111/2, 1/14, 1/2/14 or
0/18 adaptor/disc coupling options.
- Windings offered are
12-wire reconnectable
- Voltages available range
up to 690 V.
- IP22 enclosure
protection is standard, IP23 is optional at reduced ratings.
|
|
| Industrial
Class "H" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCI
4 – 3-phase |
4
pole |
250
– 380 |
281
– 475 |
| Marine
Class "F" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCM4
- 3 phase |
4
pole |
200
– 310 |
231
– 394 |
|
|
 |
|
|
 |
HC
GENERATOR RANGE : HCI5 / HCM5
- HCI/HCM 5 is a range of
4-pole, single or 2-bearing AVR controlled generators.
- Engines adaptors to SAE
00, 0, 1/2 & 1, and coupling discs to SAE 14, 18 & 21 are
offered for HCI/HCM 5
- HCKI 5 is a higher
output alternative to HCI 5, dedicated to SAE1/2 /14, 0/14 or 0/18
adaptor/disc coupling options.
- Windings offered are
12-wire reconnectable
- Voltages available range
up to 690 V.
- IP22 enclosure
protection is standard, IP23 is optional at reduced ratings.
|
|
| Industrial
Class "H" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCI
5 – 3-phase |
4
pole |
425
– 670 |
500
– 825 |
| Marine
Class "F" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCM5
- 3 phase |
4
pole |
340
– 540 |
410
– 663 |
|
|
 |
|
|
 |
HC
GENERATOR RANGE : HCI6 / HCM6
- HCI/HCM 634 is a range
of 4-pole, single or 2-bearing AVR controlled generators.
- Engine adaptors to SAE
00, 0 & 1/2, and coupling discs to SAE 14, 18 & 21 are offered
for HCI/IICM 634
- Windings offered are
6-wire reconnectable as standard, a 12-wire reconnectable alternative
is available for some applications – refer to factory for details.
- Voltages available range
up to 690 V.
- IP22 enclose protection
is standard, IP23 is optional at reduced ratings.
|
|
| Industrial
Class "H" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCI
634 |
4
pole |
800
– 1130 |
875
– 1438 |
| Marine
Class "F" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCM
634 |
4
pole |
630
– 940 |
731
– 1181 |
|
|
 |
 |
HC
GENERATOR RANGE : HCI7 / HCM7
- HCI/HCM 734 is a range
of 4-pole, single or 2-bearing AVR controlled generators.
- adaptors to SAE 00 and
0, and coupling discs to SAE 14, 18, 21 & 24 are offered for HCI/HCM
734.
- 734 is a higher output
alternative to HCI 734, dedicated to SAE 0/18, 00/18 or 00/21
adaptor/disc coupling options.
- Windings offered are
6-wire reconnectable.
- Voltages available range
up to 690 V.
- enclosure protection is
standard, IP23 is optional at reduced ratings.
|
|
| Industrial
Class "H" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCI
734 |
4
pole |
1320
– 2000 |
1500
– 2500 |
| Marine
Class "F" Continuous Ratings (kVA) |
| |
|
50Hz |
60Hz |
| HCM
734 |
4
pole |
1035
– 1625 |
1206
– 2040 |
|
|
 |
|